ATS Designers Guide
80
Current cons. mA
Device
Connected
Expansion
Description
Max. Typical
Required
voltage V
Notes
ATS1156 -
System keypad, 3 system status LED, metal
housing, with magnetic card reader (ACT600)
45 39 7,35
Each LED lit add: +9mA;
Card swipe add: +5mA.
- Wiegand reader interface, PCB only 45 32
ATS1170
ATS1190
Wiegand reader interface, with proximity reader
connected
95 65
9,6
ATS1190 -
ATS proximity Smart Card reader (do not require
interface)
50 29 7,99
ATS1192 -
ATS proximity Smart Card reader (do not require
interface), vandal resistant housing
50 29 7,99
ATS1202 -
Zone expansion module 8 input for control panel
and DGP, PCB
10 9
- Zone expansion DGP – 8 inputs and 8 outputs 53 50 6,73 Sends „Low Voltage” message at 10,5VDC
ATS1810 ATS1210/11 with 4 relays module connected 130 70 9,6
All relays active. Minimum voltage to activate relays
10,3VDC. Pooling continues up to 5,5VDC.
ATS1811 ATS1210/11 with 8 relays module connected 225 110 9,6
All relays active. Minimum voltage to activate relays
10,1VDC. Pooling continues up to 5,5VDC.
ATS1210/11
ATS1820 ATS1210/11 with 16OC module connected 90 38 6,73 All outputs active without any additional load.
ATS1220 - Zone expansion DGP – 4 inputs 53 45 6,73
ATS1230 -
Zone expander DGP - wireless devices receiver,
433MHz freq. Up to 32 detectors and 16 keyfobs
39 7,48
-
Zone expander DGP – addressable devices with
Point ID bus. Up to 32 devices.
53 50 9,5
Without Point ID load, no addressable devices
connected
ATS1290
PID bus
TS1290 with PID bus connected with max. load of
512UL
154 154 9,5
PID bus with maximum specified load of 512UL (UL
Unit Load)