36 ATS Designers Guide
Table 3-3 Data bus power supply – Maximum Range.
Current mA Belden WCAT52/54 WS108
50 261m 179m 167m
100 131m 89m 83m
150 87m 60m 56m
200 65m 45m 42m
250 52m 36m 33m
3.1.2 Device Addressing
All the functional ATS devices – DGP and RAS – communicate with the control panel
using the data bus. The data bus address space (RS485 – 32 devices) is divided into two
groups, DGP and RAS, addressed separately. The system bus compatible RAS and DGP
device list can be found in Table 1-10 and Table 1-22.
DGP addressing is carried out by setting the DIP switch on the PCB board of the device.
There can be maximum 15 DGP devices in the system, numbered 1 to 15. For the DGP
device to be visible in the system, it’s pooling needs to be enabled. The ATS1250/60
devices accept addresses 1 to 12 due to the access control DGP count limit to 12
devices. The remaining addresses can be assigned to ATS1201/03/10/11/20 DGP units.
The control panel is identified as DGP number 16. The DIP switch settings for the DGP
module addresses are presented in Table 3-4. DGP module addressing is vital for alarm
zone addressing space usage.
Table 3-4 RAS and DGP addresses and numbers in the ATS system (DIP switch
settings)
DGP Address RAS Address
Device
Number
ATS1201/03
ATS1210/11
ATS1220
ATS1250
ATS1260
ATS11xx
1
1000 1000 0000
2 0100 0100
1000
3 1100 1100 0100
4 0010 0010 1100
5
1010 1010
0010
6 0110 0110
1010
7 1110 1110 0110
8 0001 0001 1110
9
1001 1001
0001
10 0101 0101
1001
11 1101 1101 0101
12 0011 0011 1101
13
1011 -
0011
14 0111
- 1011
15 1111
-
0111
16 Control panel 1111
The RAS station addressing is done either through software, or by an appropriate setting
of the DIP switch on the device’s PCB board. The devices that can have their address set
by programming are ATS1190 and ATS1192 – smart card readers. The default address
value for their address is 16. There can be up to 16 RAS devices in the system,
numbered 1 to 16. For the RAS devices to be visible in the system, they have to be
activated by switching on the pooling of the appropriately numbered RAS device. By