22 ATS Designers Guide
Table 1-24 Listing of the access control DGP characteristics
Parameter
ATS1250 ATS1260
Number of passages 4 doors 4 lifts/ 64 floors
Number of onboard reader IF 4 4
Max. number of readers 16 16
Local DGP q-ty - 15
Onboard zones 16 16
Max. onboard zones 16 16
Max. zone quantity 16 256
Onboard outputs 4 relay.+ 8 OC 4 relay. + 8 OC
Max. output quantity 48 256
Siren output Yes Yes
Power supply 230V AC 230V AC
Housing M M
Circuit board size A A
Table 1-25 DGP technical characteristics
Parameter ATS1201 ATS1203 ATS1210/11 ATS1220 ATS1230 ATS1290 ATS1250/60
Max Power cons. 80 80 53 53 30 154 275
Avg. Power cons. 75 75 50 45 30 53 275
Operating voltage 230V AC 230V AC 12V DC 12V DC 12V DC 12V DC 230V AC
Min. voltage ±10% ±10% 10.5V DC 10.5V DC 10.5V DC 10.5V DC ±10%
Power supply unit 2A 3A - - - - 4,5A
OC output load 50mA 50mA 50mA 50mA - - 50mA
Relay contacts load 1A@30V 1A@30V 1A@30V 1A@30V - - 1A@30V
Door lock relay load - - - - - - 2A@30V
Temp. max.
o
C
50 50 50 50 60 50 50
Temp. min.
o
C
0 0 0 0 0 10 0
IP rating IP30 IP30 IP30 IP30 IP30 IP30 IP30
Humidity 95% 95% 95% 95% 90% 95% 95%
1.4 System accessories
1.4.1.1 System input and output modules.
ATS1202 8 alarm zones.
Used for control panel and DGP expansion
Dimensions: B
ATS1810
4 relay outputs. Asynchronous device, not compatible with remaining output
expansions. This module converts OC outputs into relay outputs.
Dimensions: B
ATS1811
8 relay outputs. Synchronous device, enabling cascade linking to provide additional
outputs.
Dimensions: BB
ATS1820 16 OC outputs. Synchronous device, enabling cascade linking of modules.
Dimensions: B+
ATS1821
8 OC outputs. Synchronous device, it’s not possible to cascade link the modules.
Dedicated module for communications with external communicators not integrated with
the ATS system..
Dimensions: B