Aritech ATS4000 Servisní příručka Strana 57

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 83
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 56
ATS Designers Guide 57
4.1.1.2 Step II. Connecting the system to a PC
Connection with a
PC, printer or CCTV
system
ATS2018
ATS3018
ATS4018
ATS4518
ATS3018*
ATS4018
ATS4518
NO
YES
+ATS1801/02
*- only ATS1830 memory- 1Mb
Drawing 4-2 Connecting the control panels to a computer, printer or CCTV system.
If any of the abovementioned functions is required, the control panel needs to be
equipped with the ATS1801 module – the computer/printer interface; or ATS1802 –
printer interface; This excludes the ATS2000 control panel – it doesn’t provide a
connector for the abovementioned modules, and limits the choice of memory expansions
for the ATS3000 control panel.
Monitoring and managing the system from the computer station, either remote or local;
Event printer;
Digital recorder integration;
Control panel network connection;
4.1.1.3 Step III. Users and access control range
Each memory expansion extends the system functionality through:
Increasing the number of alarm groups from 70 to 138
Increasing the number of door groups from 10 to 128
Increasing the alarm log size from 250 to 1000 entries.
Increasing the access control log from 10 to 1000 entries.
Besides that, the use of memory expansion modules increases the number of users in
the system, and provides additional functions:
IUM – storing the whole (up to 48 bits) data stream of the card;
Quick searching of the database–the ATS1831/32 expansions.
The IUM functions frees the system from limits imposed by the access card formats.
Drawing 4-3 shows a diagram of the access card range, and the number of users in the
system depending on the memory expansion. Detailed information about access cards
can be found in section 4.4.
The Table 4-3 below contains the available memory expansions and user configurations.
Because the access control DGP stores a local copy of the user database, the same
memory expansion needs to be provided for both the DGP and the control panel. Not all
memory and expansion configurations are available for every control panel. This is shown
Zobrazit stránku 56